MEW01623 Rev: - EBL128 Operating Instructions V2.0.x
50
If an ext. FBP with a built-in printer (1826) is connected, the
printer will print
47
each heavy smoke / heat alarm, e.g.:
*** Heavy smoke ***
ZONE-ADDR: 12-45 Time HH.MM Date MM-DD
Alarm text for 12-45
or
*** Heavy smoke ***
ZONE: 14 Time HH.MM Date MM-DD
Alarm text for zone 12
*** Heavy heat ***
ZONE-ADDR: 12-45 Time HH.MM Date MM-DD
Alarm text for 12-45
or
*** Heavy heat ***
ZONE: 14 Time HH.MM Date MM-DD
Alarm text for zone 14
Heavy smoke / heat alarm will be reset when the fire alarm
respectively is reset, see chapter "Alarm reset", page 53.
16.4 Key cabinet alarm
One programmable input
48
can be used to connect a key cabinet.
The fire brigade uses a key cabinet to store a key to the building.
A key cabinet alarm is like a normal fire alarm, i.e. outputs with
trigger condition "General fire alarm" will be activated.
16.4.1 Key cabinet opened before a fire alarm
If the key cabinet is opened before a fire alarm (e.g. if somebody
illegally breaks into the key cabinet), a key cabinet alarm, i.e. a "fire
alarm" will be generated.
Example; Key cabinet alarm:
ZONE: KE No. 01
Alarm from key cabinet
It will be printed like a normal fire alarm if an ext. FBP with printer is
available, see chapter "Fire alarm", page 42.
Key cabinet alarm is reset like a normal fire alarm, see chapter "Fire
alarm reset, page 53.
46
General heavy smoke / heat alarm and individual alarm points / zones.
47
The alarms will be printed like they are presented in the display, i.e. as
ZONE-ADDR or ZONE.
48
Input I0 or COM loop I/O unit 3361 can be used.