MEW01623 Rev: - EBL128 Operating Instructions V2.0.x
130
31.5 Restore weekly average to default (H8/S5)
If a sensor (analog smoke detector) is replaced without having
generated SERVICE signal, its week average sensor value has to be
restored and set to a default value. If not, the new / clean sensor will
inherit the old sensor's value. The week average sensor value has to
be restored for each replaced sensor individually. First replace the
sensor then restore the week average sensor value as soon as
possible.
The very first week average sensor value after restoring will be
calculated within one hour. Thereafter a new average sensor value
will be calculated each week.
NOTE! Authorised service personnel only, must use this menu.
Used incorrectly it can cause nuisance fire alarms from a sensor or no
fire alarm at all.
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 81.
Scroll to menu H8.
Maintenance
ACCEPT? H8
"A"
Disconnect / Re-connect COM loop
ACCEPT? S1
Scroll to menu S5.
Restore weekly average to default
ACCEPT? S5
"A"
Enter zone-address to restore: 00-00
ACCEPT?
Write the zone-address and
press "A" to accept.
E.g. "01-01"
"A"
Sensor 01-01 (tech addr 001) is restored
to default average
"A"
Enter zone-address to restore: 00-00
ACCEPT?
If more sensors shall be
restored, continue like
above. If not, press
"Return" to menu S5.
"Return"
Restore weekly average to default
ACCEPT? S5
Scroll or press "Return" to
menu H8.
"Return"
Maintenance
ACCEPT? H8
Scroll or press "Return".