Panasonic Eco Solutions Nordic AB
MEW01623 Rev: - EBL128 Operating Instructions V2.0.x
91
25.5 Re-enable zone (H2/B5)
Disabled zones are listed in menu H4/U1.
Re-enabling via this menu (H2/B5) has higher priority than automatic
re-enabling.
Zones disabled when the "New Zealand FB Silence switch" (outside
switch) is turned OFF, have to be re-enabled via menu B5 or B6
before they can activate a new alarm.
When all zones have been re-enabled, the LED "Disablements" (L8)
will be turned OFF, if there are no other disablements.
NOTE! Alarm points that have been individually disabled via menu
H2/B2 cannot be collectively re-enabled via this menu. They have to
be individually re-enabled.
If there is nothing to re-enable, --- List is empty --- will be
shown.