MEW01623 Rev: - EBL128 Operating Instructions V2.0.x
128
31.3 Disconnect / Re-connect addressable zone
interface input (H8/S3)
To avoid damage on the units and EBL128 during physical connection
/ disconnection of units, it is highly recommended to have the zone
interface input disconnected (disabled), i.e. voltage free (dead).
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 81.
Scroll to menu H8.
Maintenance
ACCEPT? H8
"A"
Disconnect / Re-connect COM loop
ACCEPT? S1
Scroll to menu S3
Disconnect / Re-connect addressable zone
interface input ACCEPT? S3
"A"
Disconnect (=0) or Re-connect (=1) addr.
zone interface input? 1 ACCEPT?
Press "0" or "1" and
press "A" to accept.
Depending on if "0" or
"1" is chosen, one of
the following will be
shown:
Disconnect addressable zone interface
input, technical address: 000 ACCEPT?
Write the COM loop
address (001-255). Press
"A" to accept.
Re-connect addressable zone interface
input, technical address: 000 ACCEPT?
E.g. "0"
"001"
"A"
Input technical address 001 disconnected
"A"
Disconnect addressable zone interface
input, technical address: 000 ACCEPT?
Do more disconnections
or press "Return".
"Return"
Disconnect (=0) or Re-connect (=1) addr.
zone interface input? 1 ACCEPT?
Write "0" or "1" and
press "A" to accept or
press "Return" menu S3.
"Return"
Disconnect / Re-connect addressable zone
interface input ACCEPT? S3
Scroll or press "Return"
to H8.
"Return"
Maintenance
ACCEPT? H8
Scroll or press "Return".