EasyManua.ls Logo

Panasonic EBL128

Panasonic EBL128
152 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Panasonic Eco Solutions Nordic AB
MEW01623 Rev: - EBL128 Operating Instructions V2.0.x
57
18 Fault
In case of a fault condition, the following has happened / will happen
in EBL128:
The buzzer in EBL128 sounds steady (continuous).
Output "R1" for routing equipment (Fault tx) is activated.
Programmable output for general fault is activated
Programmable output for general charge fault is activated if
it is a charge fault.
LED "Fault tx activated" (L11) is turned ON.
LED "General fault" (L7) is turned ON.
LEDs "Fault / Disablements Alarm devices" (L13),
"System fault" (L14) and/or "Fire brigade tx" (L15) might as
well be turned ON (depending on the type of fault).
A fault message incl. date and time is shown in the display.
NOTE! The way the date is presented could be different for
different languages.
For an alarm point / zone also the "alarm text" will be
shown.
Example of a fault message for an alarm point (e.g. a detector):
FAULT: No reply zz-aa
Date: MM-DD Time: HH:MM
Press "" to see more information:
FAULT: No reply techn. address xxx
User definable alarm text for zz-aa
Press "" to see the zone-address:
If more than one fault is activated, the text:
"More faults" is added after the time.
If a fault has been corrected before it has been
acknowledged, the "status" text: "Serviced" is added
after the time.
52
Fire alarm presentation has higher priority than the fault
messages. During fire alarm presentation the faults can be
shown via the special fire alarm menu X2, see page 46.
Faults are normally latched and have to be acknowledged, which is
done via menu H6 (see page 123). In menu (H6) can up to 200 faults
be listed:
Not serviced/corrected and not acknowledged faults
Not serviced/corrected but acknowledged faults
Serviced/corrected but not acknowledged faults
52
In EBLWin, Fault latching can be selected (default) or not selected.
Selected = each fault always have to be acknowledged. Not selected =
corrected faults will automatically be removed from the fault list (menu H6).

Table of Contents

Other manuals for Panasonic EBL128

Related product manuals