Panasonic Eco Solutions Nordic AB
MEW01623 Rev: - EBL128 Operating Instructions V2.0.x
96
25.9 Disable / re-enable alarm devices (H2/B9)
Disabled alarm devices are listed in menu H4/U1.
Outputs for alarm devices can be collectively disabled and re-enabled
via this menu. Disabled output will stay disabled, until re-enabled
again via this menu.
When all outputs type Alarm devices have been disabled, the LEDs
"Disablements" (L8) and "Fault / Disablements Alarm devices"
(L13) will be turned ON.
When all outputs type Alarm devices have been re-enabled, the LED
"Fault / Disablements Alarm devices" (L13) will be turned OFF.
NOTE! This function for alarm devices is not the same as for push
button "Silence alarm devices" (P3) – unless the option Button
"Silence alarm devices" disables alarm devices, is selected in EBLwin
System properties, see chapter "Silence Alarm devices", page 29.
This menu has higher priority than the push button "Silence alarm
devices".