Panasonic Eco Solutions Nordic AB
MEW01623 Rev: - EBL128 Operating Instructions V2.0.x
127
31.2 Disconnect / Re-connect zone line input
(H8/A2)
To avoid damage on the units and EBL128 during physical connection
/ disconnection of units, it is highly recommended to have the zone
line disconnected (disabled), i.e. voltage free (dead).
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 81.
Scroll to menu H8.
Maintenance
ACCEPT? H8
"A"
Disconnect / Re-connect COM loop
ACCEPT? S1
Scroll to menu S2
Disconnect / Re-connect zone line input
ACCEPT? S2
"A"
Disconnect (=0) or Re-connect (=1) zone
line input? 1 ACCEPT?
Press "0" or "1" and press
"A" to accept.
Depending on if "0" or
"1" is chosen, one of
the following will be
shown:
Disconnect zone line input 0 expansion
board 0 ACCEPT?
Write the 4580 board no.
(0-3) and the zone line
input no. (0-7). Press "A"
to accept.
Re-connect zone line input 0 expansion
board 0 ACCEPT?
E.g. "0"
"0"
"A"
Zone line input 0 expansion board 0
disconnected
"A"
Disconnect zone line input 0 expansion
board 0 ACCEPT?
Do more disconnections or
press "Return".
"Return"
Disconnect (=0) or Re-connect (=1) zone
line input? 1 ACCEPT?
Write "0" or "1" and press
"A" to accept or press
"Return" menu S2.
"Return"
Disconnect / Re-connect zone line input
ACCEPT? S2
Scroll or press "Return" to
H8.
"Return"
Maintenance
ACCEPT? H8
Scroll or press "Return".