Panasonic Eco Solutions Nordic AB
MEW01623 Rev: - EBL128 Operating Instructions V2.0.x
129
31.4 Acknowledge SERVICE signal (H8/S4)
See chapter "Sensors activating SERVICE signal (H4/U4)", page 107.
Indicated by LED "Service" (L12), which will be turned off when all
sensors have been acknowledged.
When a sensor (analog smoke detector) that has generated SERVICE
signal is acknowledged, the sensor will be given a default sensor value
as for a new / clean sensor, i.e. first replace the sensor then
acknowledge the service signal as soon as possible.
The very first week average sensor value after the SERVICE signal is
acknowledged will be calculated within one hour. Thereafter a new
week average sensor value will be calculated every week.
NOTE! If a sensor is replaced without activating service signal, it has
to be reset to the default sensor value via menu H8/S5, see page 130.
If there are no sensors having activated SERVICE signal,
--- List is empty --- will be shown.