133
31.8 Activate zone-address in alarm mode
(H8/S8)
One alarm point (zone-address), not a whole zone, can be manually
activated, i.e. be set in alarm mode.
NOTE! All outputs, standard and programmable, which would have
been activated by a real fire alarm from the same alarm point, will be
activated by this "manually activated" alarm as well.
According to chapter
"Access", see page 81.
Acknowledge SERVICE signal
ACCEPT? S1
Activate zone/address in alarm mode
ACCEPT? S8
Select zone: 00 address: 00
ACCEPT?
Write the zone and
address, e.g. "12-45"
Select zone: 12 address: 45
ACCEPT?
Press "A" to accept /
activate the fire alarm.
001 ZONE-ADDR 12-45 LAST ZONE 12 No. 01
"Alarm text for 12-45"
Normal fire alarm
presentation in the
EBL128 / FBP display.
If more alarm points have
to be set in alarm status,
press "Return" to select
another zone - address and
continue as above.
Select zone: 00 address: 00
ACCEPT?
Write another zone and
address, e.g. "12-34".
Select zone: 12 address: 34
ACCEPT?
Press "A" to accept / start
the fire alarm.
001 ZONE-ADDR 12-45 LAST ZONE 12 No. 01
"Alarm text for 12-45"
The LEDs "Alarms
queued" (L2) are
indicating that more than