EasyManua.ls Logo

Panasonic EBL128

Panasonic EBL128
152 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Panasonic Eco Solutions Nordic AB
MEW01623 Rev: - EBL128 Operating Instructions V2.0.x
105
Algorithm
Detectors 3308/3309, 430x and 440x, all in NORMAL mode.
Short
name
75
Normal sensitivity (3%/m) & Normal detection (15 s)
N-15
High sensitivity (2.4%/m) & Normal detection (15 s)
H-15
Low sensitivity (3.6%/m) & Normal detection (15 s)
L-15
Normal sensitivity (3%/m) & Slow detection (35 s)
N-35
High sensitivity (2.4%/m) & Slow detection (35 s)
H-35
Low sensitivity (3.6%/m) & Slow detection (35 s)
L-35
Heat algorithm, Class A1
A1
Heat algorithm, Class A2 (S)
A2
Heat algorithm, Class B (S)
B
Decision algorithm
Dec
76
Default is N-15 and A1 respectively.
Algorithm
Detector 4400 in Advanced mode.
Short name
Normal area
Normal
Clean area
Clean
Cooking-Welding area
Welding
Heater area
Heater
Smoke-Steam area
Smoke
Default is Normal.
Algorithm
Detector 4401 in Advanced mode.
Short name
Normal area
Normal
Clean area
Clean
Smoke-Steam area
Smoke
Default is Normal.
75
If some other short name is wanted, it can be changed in EBLWin. Up to
six characters can be used.
76
Analog multi detector 4300 only.

Table of Contents