MEW01623 Rev: - EBL128 Operating Instructions V2.0.x
47
Press "" (to see the next fault).
16.2.1.3 Display disablements (X3)
NOTE! Also zones in "Test mode" will be displayed via this menu.
001 ZONE-ADDR 12-45 LAST ZONE 12 No. 01
Display disablements ACCEPT? X3
Press "A"
001 ZONE-ADDR 12-45 LAST ZONE 12 No. 01
Zone XX address XX disabled
Press "" (to see the next disablement).
NOTE! After all disablements will zones in "Test mode" be
displayed.
001 ZONE-ADDR 12-45 LAST ZONE 12 No. 01
Zone in TEST MODE: 01 02 03 04
16.2.1.4 Disable zone (X4)
001 ZONE-ADDR 12-45 LAST ZONE 12 No. 01
Disable zone ACCEPT? X4
Press "A"
001 ZONE-ADDR 12-45 LAST ZONE 12 No. 01
Disable zone: 00 ACCEPT?
Write a zone number (01 99) and press "A". If more zones are to be
disabled, repeat the procedure.
16.2.1.5 Disable zone / address (X5)
This function is useful e.g. for a manual call point not to continue to
generate alarms because of a broken glass.
001 ZONE-ADDR 12-45 LAST ZONE 12 No. 01
Disable zone-address ACCEPT? X5
Press "A". E.g.:
001 ZONE-ADDR 12-45 LAST ZONE 12 No. 01
Disable zone: 00 Address: 00 ACCEPT?
Write a zone-address and press "A". If more zone-addresses are to be
disabled, repeat the procedure.
16.2.1.6 Re-enable zone (X6)
001 ZONE-ADDR 12-45 LAST ZONE 12 No. 01
Re-enable zone ACCEPT? X6
Press "A". E.g.: