Automatically after download of
site specific data (SSD) via a PC
& EBLWin. ("Warm restart")
NOTE! During the restart, the output "R1" for Fault tx will be
"activated", the supervised 24 V DC outputs S0-S1 will be not
supervised and S0-S1 programmed as normally high will be low for a
few seconds.
During the "restart", no fire alarm can be activated and the buzzer will
sound until the following text messages is show in the display:
*** EBL128 ***
Checking program memory......
And for a second (if everything is all right, else see Memory fault
below):
Booting......
A fault is now generated and the following text message will be
shown in the display:
FAULT: Restart code xx addr yyyy
Date: MM-DD Time: HH:MM
Regarding code xx and yyyy, see also page 67. This fault is also
indicated by LEDs "Fault tx activated" (L11) and "General fault" (L7).
After the fault is acknowledged (via menu H6), the LEDs will be
turned OFF if there are no other faults.