FP Mode
11-2
11.1 FPΣ Mode
11.1.1 Overview of FPΣ Mode
• FPΣ mode is a mode for using projects for the conventional model FPΣ series in FP0H.
Although some functions of FP0H are limited, compatibility with FPΣ is maintained.
Comparison of specifications
Item
Conventional
model
FP
series
FP0H series
FP
mode
FP0H mode
Values in [ ] are for
C32E only.
Program capacity (Note 1) 32K steps 24K / 32K steps
24K / 32K / [40K / 64K]
steps
Data register capacity
(Note1)
32765 words 65533 / 32765 words
65533 / 32765 / [24573 /
12285] words
Automatic
backup in
case of
power outage
(Note 2)
Internal
relay
R2480 to R255F
(Fixed)
R2480 to R255F
(Fixed)
R5040 to R511F
[R2480 to R255F]
Data
register
DT32710 to DT32764
(Fixed)
DT32710 to DT32764
(Fixed)
[DT11970 to DT12284
DT24258 to DT24572]
DT32450 to DT32764
DT65218 to DT65532
(Note 2)
Pulse/PWM output setting
(System register no. 402)
No setting Cannot be set. Can be set.
Positioning control mode
(System register no. 407)
Cannot be set.
FPΣ compatible
instruction mode
(Fixed)
Select Table setting mode
or FPΣ compatible
instruction mode.
Values when
system
registers are
initialized
No.7 248 (Fixed) 248 (Fixed)
[C32]
Initialize according to
system register no. 1.
[C32E]
504 (Fixed)
No.8 32710 (Fixed) 32710 (Fixed)
Initialize according to
system register no. 0.
No.407 Cannot be set.
FPΣ compatible
instruction mode
Table setting mode
No.430 to
No.433
Cannot be set. No setting 1 ms
(Note 1): Program capacities and data register capacities can be changed by the setting of the system register no. 0.
(Note 2): In the FP0H mode, the automatic backup areas for internal relays and data registers vary according to the
settings of system register nos. 0 and 1.