7.2 FP Compatible Instruction Mode Control Instruction
7-13
7.2.2 [F171(SPDH)] Pulse Output (Home Return)
This instruction outputs pulses from a specified pulse output channel according to specified
parameters.
Instruction format
Operand
Operand Settings
S
Starting number of the area in which data tables are registered
n
Target channel for pulse output
Memory area type that can be specified
Operand WX WY WR WL SV EV DT LD I
Constant
Index
modifier
K H
Outline of operation
• Outputs pulses from a specified channel when a corresponding control active flag is OFF
and the execution condition is ON.
• The control code, initial speed, maximum speed, acceleration/deceleration time, and
deviation counter clear signal are specified by creating data table described on the next
page using a user program.
• Switches the frequency from the initial speed to the maximum speed in the specified
acceleration/deceleration time. At the time of deceleration, switches the frequency with the
same inclination as that for acceleration.
• For setting the frequency to 50 kHz or more, specify the duty of 1/4 (25%).