890CS Resistor Selection
Choose from the following tables listing recommended resistor kits.
890CS Dynamic Braking Resistor Kits - USA/Canada
These kits (complete with cover) are designed for stopping a motor at full load current from base speed
with two times motor inertia, three times in rapid succession in accordance with NEMA ICS 3-302.62
Dynamic Braking Stop option.
Frame
Size
Drive
Amps
(A)
Drive
Rating
(Hp)
Brake
Level
(V)
Peak
Amps
(A)
Minimum
Ohms
(Ω)
SSD
Part
Number
Dimensions
L x W x H
(inches)
Resistance
(Ω)
Rated
Amps
(A)
208/230 Vac
B 32 10 390 20 19.5 CZ353192 10 x 4 x 5 27 3.6
B 54 20 390 40 9.8 CZ353195 12 x 7 x 5 10 8.5
D 108 40 390 75 5.2 CZ353197 12 x 13 x 5 6 15
D 162 60 390 100 3.9 CZ353198 19 x 10 x 5 5 18
460 Vac
B 32 25 770 20 38.5 CZ353181 10 x 7 x 5 54 3.6
B 54 45 770 40 19.3 CZ353184 12 x 10 x 5 22.5 7.2
D 108 90 770 75 10.3 CZ353186 19 x 10 x 5 12 13
D 162 135 770 100 7.7 CZ353188 27 x 10 x 5 9 18