Programming  
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D  Page D-111 
8 
9 
10 
11 
 
B 
C 
D 
1 
2 
3 
4 
5 
6 
7 
E 
REGEN CONTROL 
SETUP::MOTOR CONTROL::REGEN CNTRL 
Designed for 4Q Regen Control Mode. 
This function block is used to setup, sequence and monitor  the operation of the drive when used in 4Q Regen Control Mode. 
Parameter Descriptions 
PRECHARGE CLOSED 
PREF: 114.01  Default: TRUE  Range: FALSE / TRUE 
This parameter is used to indicate the external precharge contactor is closed, i.e. the external precharge resistor is no longer in 
circuit. 
DC VOLTS DEMAND 
PREF: 114.02  Default: 720V  Range: 0 to 1000V 
Use this to set the demanded dc link volts for the common dc bus. It must be set higher than the peak of the mains supply, but 
lower than the overvolts (820V on 400V products, 410V on 230V products). 
BRAKE MODE 
PREF: 114.15  Default: FALSE  Range: FALSE / TRUE 
Setting this parameter True allows the drive to generate energy into the mains in common dc link systems. The regeneration 
occurs when the dc link is higher than the DC VOLTS DEMAND level. In this mode the drive will not draw energy from the 
mains. The drive acts purely as a braking unit. 
SYNCHRONIZING 
PREF: 114.09  Default: FALSE  Range: FALSE / TRUE 
This diagnostic reads True during the mains synchronisation period. This occurs when the drive is first run in 4Q Regen 
Control Mode. This synchronising period lasts for 100ms. 
SYNCHRONIZED 
PREF: 114.10  Default: FALSE  Range: FALSE / TRUE 
This diagnostic reads True when mains synchronisation has been successfully completed. 
PHASE LOSS 
PREF: 114.11  Default: FALSE  Range: FALSE / TRUE 
This diagnostic reads True if the drive suspects there is a missing input phase from the mains supply.