Associated Equipment  
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D  Page 6-9 
8 
9 
10 
11 
 
B 
C 
D 
1 
2 
3 
4 
5 
6 
7 
E 
890CS Dynamic Braking Resistors - Europe 
These resistor sets (complete with cover) are designed for stopping the system at rated power. 
They are rated for 10 seconds in a 100 seconds duty cycle.  
IMPORTANT  The continuous rating of the quoted resistor is not to be exceeded under repetitive loading 
conditions. 
Frame 
Size 
Drive 
Amps
(A) 
Drive 
Rating 
(kW) 
Brake 
Volts 
(V) 
Peak 
Amps
(A) 
Minimum 
Ohms 
(Ω) 
Cressall 
Part 
Number 
Dimensions 
L x W x H 
 (mm) 
Resistance
 
(Ω)  
Rated 
Amps
(A) 
Rated 
Power 
(W) 
208/230 Vac 
B  32  7.5  390  20  19.5  HP1-24R  505 x 138 x 135.5  24  8  1500 
B  54  15  390  40  9.8  HP1-12R  505 x 138 x 135.5  12  11  1500 
D  108  30  390  75  5.2  HP1-5R6  505 x 138 x 135.5  5.6  16  1500 
D  162  45  390  100  3.9  HP2-4R7  505 x 138 x 135.5  4.7  25  3000 
380/415 Vac 
B  32  15  770  20  38.5  HP1-47R  505 x 138 x 135.5  47  5.6  1500 
B  54  30  770  40  19.3  HP1-24R  505 x 138 x 135.5  24  8  1500 
D  108  60  770  75  10.3  HP2-12R  505 x 233 x 135.5  12  16  3000 
D  162  90  770  100  7.7  HP3-8R2  505 x 327 x 135.5  8.2  23  4500 
500 Vac 
B  32  18  830  20  41.5  HP1-47R  505 x 138 x 135.5  47  5.6  1500 
B  54  37  830  40  20.8  HP1-24R  505 x 138 x 135.5  24  8  1500 
D  108  75  830  75  11.1  HP2-12R  505 x 233 x 135.5  12  16  3000 
D  162  110  830  100  8.3  HP3-10R  505 x 327 x 135.5  10  21  4500