EasyManua.ls Logo

Parker 890SD - Earthing;Safety Details

Parker 890SD
586 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Specifications
Page E-26 890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
8
9
10
11
A
B
C
D
1
2
3
4
5
6
7
E
Earthing/Safety Details
Earthing
Permanent earthing is mandatory on all units.
Use a copper protective earth conductor 10mm² minimum cross-section, or install a second conductor in
parallel with the protective conductor to a separate protective earth terminal
The conductor itself must meet local requirements for a protective earth conductor
Input Supply
Details
(TN) and (IT)
Drives with or without external filters are suitable for use on earth (TN) or non-earth referenced (IT)
supplies
Earth
Leakage
Current
>10mA (all models)

Table of Contents