TORQUE LIMIT 
SETUP::MOTOR CONTROL::TORQUE LIMIT 
Designed for all Motor Control Modes. 
This function block allows you to set the maximum level of motor rated torque which is allowed before torque limit action 
occurs. 
If the estimated motor torque is greater than the ACTUAL POS LIM value, the motor speed is controlled to maintain the 
torque at this level. A similar situation occurs if the estimated motor torque is less that the ACTUAL NEG LIM value. 
The torque limit function block has separate positive and negative torque limits. In addition, a symmetric main torque limit is 
also provided. 
The lowest positive and negative torque limits (including any current limit or inverse time current limit action) is indicated in 
the ACTUAL POS LIM and ACTUAL NEG LIM diagnostic. These are the final limits used to limit motor torque. 
Parameter Descriptions 
POS TORQUE LIM 
PREF: 83.01  Default: 150.00 %  Range: -300.00 to 300.00 % 
This parameter sets the maximum allowed level of positive motor torque. 
NEG TORQUE LIM 
PREF: 83.02  Default: -150.00 %  Range: -300.00 to 300.00 % 
This parameter sets the maximum allowed level of negative motor torque 
MAIN TORQUE LIM 
PREF: 83.03  Default: 150.00 %  Range: 0.00 to 300.00 % 
This parameter sets the symmetric limit on the maximum allowed motor torque. 
FAST STOP T-LIM 
PREF: 83.07  Default: 150.00 %  Range: 0.00 to 300.00 % 
This parameter sets the torque limit used during a Fast Stop. 
SYMMETRIC LIM 
PREF: 83.04  Default: FALSE  Range: FALSE  / TRUE/ 
When TRUE, the NEG TORQUE LIM is forced to reflect the POS TORQUE LIM parameter.