890CD Minimum Control Connections
Minimum Connections
Connect X14/04 to a clean,
external earth
Speed Reference
Connect a 10kΩ
potentiometer at terminal
X12:
X12/01 : Low (CCW)
X12/04 : Wiper
X12/08 : High (CW)
Connect the shield to
earth/ground at the control
bracket.
OR
External 2-wire speed
reference between:
X12/01 : negative
X12/04 : positive
Connect the shield to
earth/ground at the control
bracket.
Sequencing
RUN (maintained contact)
X14/03 : 24V
X15/02 : RUN
890CD COMMON BUS DRIVES
24V DC
Speed
Potentiometer
Start
External
Reference
Start
Control bracket
for terminating all
control wiring shields
24V DC24V DC