Programming 
Page D-90  890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D 
8 
9 
10 
11 
 
B 
C 
D 
1 
2 
3 
4 
5 
6 
7 
E 
POSITION LOOP 
SETUP::MOTOR CONTROL::POSITION LOOP 
This block controls the position of the motor. It compares a position demand, with position feedback, and generates a speed 
demand dependent on the difference. Note that the function blocks Move to Master, Phase Inch, Phase Move, Phase Move 
Abs, etc. will not work if this block is not enabled (PREF 3879). 
 
Parameter Descriptions 
ENABLE 
PREF: 121.07  Default: FALSE  Range: FALSE / TRUE 
Set True to enable the position loop to operate. 
PROP GAIN 
PREF: 121.01  Default: 10.0  Range:  
The position loop proportional gain. 
INTEGRAL TIME 
PREF: 121.02  Default: 500.0 ms  Range:  
The position loop integral time constant. 
INTEGRAL DEFEAT 
PREF: 121.03  Default: FALSE  Range:  
When TRUE, this parameter sets the position loop integral to 0.0 and prevents it from operating. 
LIMIT 
PREF: 121.11  Default: 10.00 %  Range: 0.00 to 300.00 % 
This parameter sets a symmetric clamp as a percentage of maximum speed, to limit the maximum position loop output of the 
block (PID Output). 
POSITION DEMAND 
PREF: 121.15  Default: —.xx deg  Range: —.xx deg 
This diagnostic shows the input position demand. 
TOTAL OFFSET 
PREF: 121.14  Default: —.xxxx  Range: —.xxxx 
This diagnostic shows the total position offset from the phase control blocks, Phase Inch, Phase Move, Phase Offset & Phase 
Tuning.