EasyManua.ls Logo

Parker 890SD - 1 Parameter Table: PREF Number Order

Parker 890SD
586 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Programming
Page D-156 890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
8
9
10
11
A
B
C
D
1
2
3
4
5
6
7
E
1Parameter Table: PREF Number Order
PREF Name Block Type Range Default ro\rw Notes
1.03 TYPE ANALOG INPUT 1 ENUM 0 : -10..+10 V
1 : 0..+10 V
-10..+10 V rw
1.06 VALUE ANALOG INPUT 1 REAL _.x -100.0 % ro Output
2.03 TYPE ANALOG INPUT 2 ENUM 0 : -10..+10 V
1 : 0..+10 V
-10..+10 V rw
2.06 VALUE ANALOG INPUT 2 REAL _.x -100.0 % ro Output
3.03 TYPE ANALOG INPUT 3 ENUM 0 : -10..+10 V
1 : 0..+10 V
2 : 0..20 mA
3 : 4..20 mA
-10..+10 V rw
3.04 BREAK ENABLE ANALOG INPUT 3 BOOL 0 : FALSE
1 : TRUE
FALSE rw
3.05 BREAK VALUE ANALOG INPUT 3 REAL -300.00 to 300.00 % 0.00 % rw
3.06 VALUE ANALOG INPUT 3 REAL _.x -100.0 % ro Output
3.07 BREAK ANALOG INPUT 3 BOOL 0 : FALSE
1 : TRUE
FALSE ro Output
4.03 TYPE ANALOG INPUT 4 ENUM 0 : -10..+10 V
1 : 0..+10 V
2 : 0..20 mA
3 : 4..20 mA
-10..+10 V rw
4.04 BREAK ENABLE ANALOG INPUT 4 BOOL 0 : FALSE
1 : TRUE
FALSE rw
4.05 BREAK VALUE ANALOG INPUT 4 REAL -300.00 to 300.00 % 0.00 % rw
4.06 VALUE ANALOG INPUT 4 REAL _.x -100.0 % ro Output
4.07 BREAK ANALOG INPUT 4 BOOL 0 : FALSE
1 : TRUE
FALSE ro Output
5.06 VALUE ANALOG INPUT 5 REAL _.x -100.0 % ro Output
6.01 VALUE ANALOG OUTPUT 1 REAL -300.00 to 300.00 % 0.00 % rw

Table of Contents