Programming  
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D  Page D-27 
8 
9 
10 
11 
 
B 
C 
D 
1 
2 
3 
4 
5 
6 
7 
E 
DYNAMIC BRAKING 
SETUP::MOTOR CONTROL::DYNAMIC BRAKING 
Designed for all Motor Control Modes. 
The dynamic braking function block controls the rate at which energy from a regenerating motor is dumped into a resistive 
load. This dumping prevents the dc link voltage reaching levels which would cause an Overvoltage trip. 
Parameter Descriptions 
ENABLE  
PREF: 99.01  Default: TRUE  Range: FALSE / TRUE  
Enables operation of the dynamic braking block. 
BRAKE RESISTANCE  
PREF: 99.03  Default: 100.00 Ohm  Range:0.01 to 300.00 Ohm  
The value of the dynamic braking load resistance. 
BRAKE POWER  
PREF: 99.04  Default: 0.1 kW  Range: 0.1 to 510.0 kW  
The power that the load resistance may continually dissipate. 
1SEC OVER RATING 
PREF: 99.05  Default: 25  Range: 1 to 40   
Multiplier that may be applied to BRAKE POWER for power overloads lasting no more than 1 second. 
INT DB RESISTOR  
PREF: 99.07  Default: TRUE  Range: FALSE / TRUE  
For futrue use only. Set to FALSE if an external dynamic brake resistor is fitted. 
BRAKING  
PREF: 99.06  Default: FALSE  Range: FALSE / TRUE  
A read-only parameter indicating the state of the brake switch.