Sequencing Logic
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D Page B-11
8
9
10
11
A
B
C
D
1
2
3
4
5
6
7
E
Enable Ramp Output, Enable Ramp, Enable Ramp Input
Not implemented. The state of these bits must be set (=1) to allow this feature to be added in the future.
Reset Fault
Replaces the REM TRIP RESET parameter on the SEQUENCING LOCIC function block. When Set (=1)
is the same as:
REM TRIP
RESET
= TRUE
When Cleared (= 0) is the same as :
REM TRIP
RESET
= FALSE
Remote
Not implemented. It is intended to allow the PLC to toggle between local and remote. The state of this must
be set (=1) to allow this feature to be added in the future.
Example Commands
047F hexadecimal to RUN
047E hexadecimal to STOP