Trips and Fault Finding
Page 10-4 890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
8
9
10
11
A
B
C
D
1
2
3
4
5
6
7
E
Trips Table
The following trips may occur to protect the drive.
6511
Keypad
Display
6901
Keypad
Display
Description Possible Reason for Trip
DCHI OVERVOLTAGE The drive internal dc link
voltage is too high
The supply voltage is too high
Trying to decelerate a large inertia load too quickly
The brake resistor is open circuit
DCLO UNDERVOLTAGE The drive internal dc link
voltage is too low
The supply voltage is too low
The supply has been lost
A supply phase is missing