Trips and Fault Finding
Page 10-24 890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
8
9
10
11
A
B
C
D
1
2
3
4
5
6
7
E
Alert Message IDs
ID Message Reason
6901 Keypad 6511 Keypad
43
SUPER USER
TRUE
SUPR Reserved for Parker SSD Drives.
44
INCOMPATIBLE
POWER BOARD
ERR6
Power board 500v and/or underlap signals
incompatible with selected product code.
45
CALIBRATION
CHECKSUM FAIL
CAL The control board calibration data is invalid.
46
INCOMPATIBLE
PCB
PCB
Software is not compatible with this version of
control card PCB.
47
INCOMPATIBLE
POWER BOARD TYPE
TYPE Stack has been marked as a 650 or Baldor stack
48
INCOMPATIBLE
EEPROM FLAGS
FLGS
Reserved flags in stack eeprom are not zero.
See comms command ri.
49
INCOMPATIBLE
POWER BOARD CODE
CODE
Product code not compatible with this version
of software.