890CS & 890CD Common Bus Units   
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D  Page 4-11 
8 
9 
10 
11 
 
B 
C 
D 
1 
2 
3 
4 
5 
6 
7 
E 
8 
9 
1 
2 
3 
4 
5 
6 
E 
 
 
 
 
 
 
 
 
 
 
Caution 
 
The 890CS Common Bus Supply is factory-fitted with a safety bung to 
terminals DC+ and DC- which maintains the IP20 rating. Leave this bung 
connected unless the terminals are to be used. 
 
Refer to the 890 Installation Kit for earth/ground fixing details. Fit the appropriate parts. 
 
Each unit must be permanently earthed according to EN 50178. 
 
For permanent earthing: 
A cross-section conductor of at least 10mm² is required.  This can be achieved either by using a single 
conductor (PE) or by laying a second conductor though separate terminals (PE2 where provided) and 
electrically in parallel.