PREF Name Block Type Range Default ro\rw Notes
21.01 V/F SHAPE FLUXING ENUM 0 : LINEAR LAW
1 : FAN LAW
2 : USER DEFINED
LINEAR LAW rw
21.03 FIXED BOOST FLUXING REAL 0.00 to 25.00 % 0.00 % rw 3
21.04 AUTO BOOST FLUXING REAL 0.00 to 25.00 % 0.00 % rw
21.08 ACCELRTN BOOST FLUXING REAL 0.00 to 25.00 % 0.00 % rw
21.09 ENERGY SAVING FLUXING BOOL 0 : FALSE
1 : TRUE
FALSE rw
21.10 USER FREQ 1 FLUXING REAL 0.0 to 100.0 % 10.0 % rw
21.11 USER VOLTAGE 1 FLUXING REAL 0.0 to 100.0 % 10.0 % rw
21.12 USER FREQ 2 FLUXING REAL 0.0 to 100.0 % 20.0 % rw
21.13 USER VOLTAGE 2 FLUXING REAL 0.0 to 100.0 % 20.0 % rw
21.14 USER FREQ 3 FLUXING REAL 0.0 to 100.0 % 30.0 % rw
21.15 USER VOLTAGE 3 FLUXING REAL 0.0 to 100.0 % 30.0 % rw
21.16 USER FREQ 4 FLUXING REAL 0.0 to 100.0 % 40.0 % rw
21.17 USER VOLTAGE 4 FLUXING REAL 0.0 to 100.0 % 40.0 % rw
21.18 USER FREQ 5 FLUXING REAL 0.0 to 100.0 % 50.0 % rw
21.19 USER VOLTAGE 5 FLUXING REAL 0.0 to 100.0 % 50.0 % rw
21.20 USER FREQ 6 FLUXING REAL 0.0 to 100.0 % 60.0 % rw
21.21 USER VOLTAGE 6 FLUXING REAL 0.0 to 100.0 % 60.0 % rw
21.22 USER FREQ 7 FLUXING REAL 0.0 to 100.0 % 70.0 % rw
21.23 USER VOLTAGE 7 FLUXING REAL 0.0 to 100.0 % 70.0 % rw
21.24 USER FREQ 8 FLUXING REAL 0.0 to 100.0 % 80.0 % rw
21.25 USER VOLTAGE 8 FLUXING REAL 0.0 to 100.0 % 80.0 % rw
21.26 USER FREQ 9 FLUXING REAL 0.0 to 100.0 % 90.0 % rw
21.27 USER VOLTAGE 9 FLUXING REAL 0.0 to 100.0 % 90.0 % rw
21.28 USER FREQ 10 FLUXING REAL 0.0 to 100.0 % 100.0 % rw
21.29 USER VOLTAGE 10 FLUXING REAL 0.0 to 100.0 % 100.0 % rw