890SD Standalone Drive  
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D  Page 5-15 
8 
9 
10 
11 
 
B 
C 
D 
1 
2 
3 
4 
5 
6 
7 
E 
Power Connections - 890SD Standalone Drive 
SUPPLY  MOTOR 
SUPPLY
L1 L2 L3
 
MOTOR
M1 M2 M3
 
L1, L2, L3 
Connect 3-phase supply in any order. 
Maximum wire sizes: 
Frame B: 6mm
2
 / 10AWG, 0.5-0.9Nm / 0.4-0.7lbf 
Frame C: 10mm
2
 / 8AWG, 1.2Nm / 0.9lbf 
Frame D: 16mm
2
 / 4AWG, 2-4Nm / 1.5-3lbf 
M1 (U), M2 (V), M3 (W). 
Connect to the motor in any order. 
Maximum wire sizes: 
Frame B: 6mm
2
 / 10AWG, 0.5-0.9Nm / 0.4-0.7lbf 
Frame C: 10mm
2
 / 8AWG, 1.2Nm / 0.9lbf 
Frame D: 16mm
2
 / 4AWG, 2-4Nm / 1.5-3lbf 
DC+ / DC- Bottom Terminals  - Option 
DC+ DC-
 
These terminals can be used for link monitoring and for link 
sharing between 890SD drives - caution: refer to the Link Shairing 
Application note for limitations. 
 
Use correctly rated wire - refer to Appendix E. 
Maximum wire sizes: 
Frame B: 6mm
2
 / 10AWG, 0.5-0.9Nm / 0.4-0.7lbf 
Frame C: 10mm
2
 / 8AWG, 1.2Nm / 0.9lbf 
Frame D: 16mm
2
 / 4AWG, 2-4Nm / 1.5-3lbf