AS-i EtherNet/IP Gateway
Command Interface
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
Issue date - 24.4.2007
59
8.3.1.3 Write 1 16-bit Slave out.Data (WR_7X_OUT)
With this command, the four 16 bit channels of an AS-i output slave according to 
the slave profile (S-7.3, S-7.4, S-7.5, S-7.A.8, S.A.9, S-7.A.A) can be written.
8.3.1.4 Read 1 16-bit Slave out.Data (RD_7X_OUT)
With this command, the four 16 bit channels of an AS-i output slave according to 
the slave profile (S-7.3, S-7.4, S-7.5, S-7.A.8, S.A.9, S-7.A.A) can be read out of 
the AS-i/EtherNet/IP Gateway.
Request
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
150
16
2T – circuit
3 – 0 slave address
Response
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
150
16
2T result
3 channel 1, high byte
……
10 channel 4, low byte
Request