AS-Interface
Command Interface
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
Issue date - 24.4.2007
90
8.3.5.16 Write AS-i slave extended ID1 (WRITE_XID1)
With this call, the extended ID1 code of an AS-i slave with address "0" can be writ-
ten directly via the AS-i cable. The call is intended for diagnostic purposes and is 
not required in the normal master mode.
The AS-i master passes the extended ID1 code on to the AS-i slave without any 
plausibility check.
8.3.6 Other commands
8.3.6.1 Overview of the commands
Request
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
13F
16
2T – circuit
3– xID1
Response
Byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
13F
16
2T result
Values for command
see page Command Value Meaning
Req 
Len
Res 
Len
page 90 Other commands
page 91 IDLE
00
16
No request 2 2
page 91 READ_IDI
41
16
Read IDI 2 36
page 92 WRITE_ODI
42
16
Write ODI 34 2
page 92 READ_ODI
56
16
Read ODI 2 34
page 93 SET_OFFLINE
0A
16
Set_Off-Line_Mode 3 2
page 94 SET_DATA_EX
48
16
Set_Data_Exchange_Active 3 2
page 94 BUTTONS
75
16
Disable Pushbuttons 3 2
page 94 FP_PARAM
7D
16
„Functional Profile“ Param. ≥3 ≥2
page 95 FP_DATA
7E
16
„Functional Profile“ Data ≥3 ≥2
page 96 INVERTER
7C
16
Configure Inverter Slaves 12 4
page 96 MB_OP_CTRL_WR_FLAGS 0x85 Write Flags ≥52
page 97 MB_OP_CTRL_RD_FLAGS 0x86 Read Flags 4 ≥3
page 97 RD_MFK_PARAM 0x59 Read SEW MFK21 Parameter 6 ≥3