C-15
MacBAT 5 – USER GUIDE. Version 1.0
Technical parameters for the cables:
CT6 temperature sensor and EPS external pressure sensor – factory mounted cable, maximum length 10 meters.
Digital inputs; DI, LF, NAMUR, SCR:
• LIYCY 2 x 0,25 - 0,5 mm
2
or
• LIYCY 4 x 0,25 - 0,5 mm
2
.
Communication ports COM1, COM2, powering the device, DO outputs:
• LIYCY 2...10 x 0,50 mm
2
– max 150 m
• LIYCY 6...10 x 0,75 mm
2
– max 200 m
Or paired cables:
• LIYCY-P 2...5 x 2 x 0,34 mm
2
– max 100 m
• LIYCY-P 2...5 x 2 x 0,50 mm
2
– max 150 m
• LIYCY-P 2...5 x 2 x 0,75 mm
2
– max 200 m.
Amount of wires required for connection:
• 2 wires – only powering the EVC and internal modem
• 4 wires – powering the EVC and transmission on single RS485 channel
• 6 wires – powering the EVC and transmission on both RS485 channels
• 7-10 wires – powering the EVC, transmission ports and DO outputs