3-62 Monitoring and Diagnostics VisualMotion 9 Troubleshooting Guide
DOK-VISMOT-VM*-09VRS**-WA02-EN-P
!100 Reset Command Parameter
Global variables are flashed to memory by setting C-0-0082 to a binary 3.
This communication error is issued when a second binary 3 is set in
C-0-0082 without first setting the parameter to 0.
!101 Read only From This Port
This communication error is issued when an attempt is made to access a
control set to read-only.
!102 Does Not Match Password Requirements
This communication error is issued when an invalid character is used
while entering the password to change the access level of a serial or
network connection.
!103 Bit combination not valid
This communication error is issued if A-0-0004 bit 5=1 (Enable Measuring
Wheel Services) and bit 11=1(Position using Secondary Encoder). When
enabling a secondary encoder as the primary feedback device for an axis,
the position bit (11) can not be set to 1. This would cause a conflict in
positioning for the secondary encoder.