Menu parameters list "Set" 2-2
Menù
label
Par LabelDescription U.m.
Range
Default KCTR PW
Address
min max
di
114 FAnC
State of input "Setpoint 2" (terminals 13-14)
On: Contact closed. Required to produce water at temperatures
necessary for the operation of the fan coil.
Off: Open contact. Production of water at the temperature required to
operate the only radiating system.
---
Read
value
8963
115 nigt
Input Status "Night mode" (terminals 9-10)
On: Contact closed. Limitation maximum working frequency of the
compressor
Off: Open contact. No limitations on frequency
---
Read
value
8962
116
COOL
Input Status "Remote Cool / Heat" (terminals 11-12)
On: Contact closed. See setting par. 101 "MOdE"
Off: Open contact. See setting par. 101 "MOdE"
---
Read
value
8966
117 OnOF
State external contact "Remote On / Off"
On: Contact closed. Enable controls on / off of USER INTERFACE
(KCTR and if installed)
Off: Open contact. Activate only the function of antifreeze
---
Read
value
8965
dEHU
119 S rH Room humidity set point (active only with KCTR installed) % 30 90 60 X 16392
120 d rH
Differential on room humidity set point (active only with KCTR
installed)
% 1 20 5 S 16393
SAni
122 ESAn
DHW Production:
On: Enabled
Off: Not enabled
- Off On On X 16395
123 COnt
DHW Control:
0: Control through NTC probe
1: closed contact = DHW requested (through thermostat in the
storage domestic hot water),
2: open contact = DHW requested (through thermostat in the storage
domestic hot water)
- 0,1,2 1 S 16396
124 OnP
Beginning of period DHW priority:
Now a day on which the production of domestic hot water has priority
over climate
h:
min
00:00 23:59 00:00 S 16397
125 OFFP
End of the period DHW priority:
Time of the day to which the production of domestic hot water has
priority over climate
h:
min
00:00 23:59 23:59 S 16398
126 SEtS DHW Set point (storage domestic hot water) ° C 10 60 50 16399
127 diFS Differential on DHW Set point (storage domestic hot water) ° C 1 15 5 S 16400
128 tUSA Heat pump water delivery set point for DHW production ° C SEtS 60 55 16401
129 3UAY
Voltage output state W.V.Sanitary (clamp H):
On: H-N=230 V
Off: H-N=0 V
---
Read
value
8979
130 dELP
DHW production circulator delay
Activation delay time of pump 1, respect to activation of the output
W.V.Sanitary
min 0 9 0 S 16402
131 dELE
DHW production integrated electric heater delay
Delay time from beginning of DHW production with HP, where the
DHW electric heater is activates, as support for reaching the set
point.
If set = 0 function disabled
min 0 120 0 S 16403
132 SEtE DHW production integrated electric heater set point ° C 10 70 50 S 16404
X=Parameter also available on KCTR
S = Password service (48)
70
Section I :: User
EN