Menu parameters list "Set" 2-2
Menù
label
Par LabelDescription U.m.
Range
Default KCTR PW
Address
min max
SAni
133 CYCA
Frequency activation heat treatment ACS (Legionella)
How often should the treatment be carried out legionella. If 0, the
function is disabled
day 0 30 0 S 16405
134 SEtA Set point heat treatment DHW (
legionnaires
) °C 50 70 60 S 16407
135 tiMA
Period activation heat treatment (SWH antilegionnaires)
Minimum time continued, in which the temperature of the water in the
accumulation is maintained higher than the set point
min 1 30 15 S 16407
136
HouA
Orario attivazione trattamento termico ACS (antilegionella)
h:
min
00:00 23:59 02:00 S 16408
EHS
137 OPEr
Activation mode of the heat generators:
0: Disabled additional generator
1: When the additional generator activates, the heat pump turns off.
2: When the additional generator activates, the heat pump remains on.
- 0,1,2 0 S 16409
138 SEtO
Bivalence set point (additional generator):
External temperature at which the free contact can be activated. Heat
Source (clamps F-L)
° C -15 10 5 S 16410
139 dELt
Bivalence delay (additional generator):
On-going time where the external temperature is below the Bivalence
set point, until the free contact activates. Heat Source (clamps F-L)
min 1 120 30 S 16411
PUMP 140 P1Mb
Management Pump 1
0: Management by code
1: Management of Modbus
2: Management of the combined code and Modbus
0 2 0 S 16488
AL
AMbt
Failure of the environment temperature probe KCTR (see paragraph
10.2)
9004
AMbH
Failure of the environment humidity probe KCTR (see paragraph
10.2)
9005
OUtA
Failure of the external temperature probe KCTR (see paragraph
10.2)
9006
OUtU
Failure of the outlet water temperature probe KCTR (see paragraph
10.2)
9007
InU
Signal error “Temp. Water Supply System” (clamps 3-4) see para-
graph 10.2)
9008
SAnt
Failure of the sanitary accumulation temperature probe KCTR (see
paragraph 10.2)
9009
HP
Heat pump error. Error code on the PCB display (see paragraph
10.3)
9010
rEmC
Remote controller connecting error (see paragraph 10.2)
9011
CONd
Condensation risk for the radiant cooling system (see paragraph
10.2)
9013
SUrr
Overheating risk for the radiant heating system (see paragraph 10.2)
9014
Menu parameters list “Set”:
X=Parameter also available on KCTR
S = Password service (48)
71
Section I :: User
EN