V-21
C
ONTROL
S
YSTEMS
Select
temperature
compensation.
Set temperature
compensation.
Menu Detailed description Display
SW 8 OFF : Monitor the setting temperature compensation value
under the Heating mode.
SW 8 ON : Set the setting temperature compensation value.
Setting temperature compensation value of the heating operation:
Compensate the setting temperature used for heating operation
control.
(ex :User setting temperature 30°. Heating operation compensation
temperature 5°.
→
Heating operation control based on the set
temperature of 35°.)
Select temperature compensation values :
1) 0 – Use indoor unit PCB setting value
2) 1 – Use wired remote controller setting value
Temperature compensation: -9~9 °C
SW 8 OFF / ON: Monitor if central control is in use.
(Check the indoor unit PCB switch setting status)
0: Use central control
1: No central control used
SW 8 OFF / ON : Monitor if the drain pump is in use.
(Check the indoor unit PCB switch setting status)
0: Drain pump use
1: No drain pump used
SW 8 OFF / ON: Monitor if electric heater is in use.
(Check the indoor unit PCB switch setting status)
0: Electric heater use
1: No electric heater used
SW 8 OFF / ON: Monitor if hot water control is in use.
(Check the indoor unit PCB switch setting status)
0: Hot water control use
1: No hot water control used
SW 8 OFF / ON: Display connected indoor units quantity.
SW 8 OFF / ON: Display wired remote controller softwear version.
❈ In case of indoor unit group control, only menu 4, 13, 14 can be available.