S&C Instruction Sheet 461-504 115
Troubleshooting
STEP 6. The Clear Service Now dialog box will appear with the following message:
“Before proceeding with the Service Now Reset procedure, the TripSaver
II Cutout-Mounted Recloser must be placed on a workbench in the horizontal
position with the trunnion pointing up.“ See Figure 158.
The TripSaver II recloser must be continuously powered with the ac power
module until a Permanent Fault simulation is completed. If the recloser is
disconnected from power at any time during the procedure, the Service Now
Reset procedure will not be successful.”
After confirming the TripSaver II recloser is in the horizontal position with
the trunnion pointing up, and that it is powered with the ac adapter, click on
the Ok button.
Figure 158. The Clear Service Now dialog box.