List of Setup Parameters VC 1100
Version 2 parqalist/VC1100E
5-6 C01 / C02 - C11 / C12 © Schenck VIBRO GmbH, D-64273 Darmstadt, Juni 98
I 02 Channel B
Choises : Y, N
Function : Enable or disable Channel B.
Y = Yes Channel B is active
N = No Channel B is not active
I02 = Y : For measured value acquisition, connect a pickup to
channel B.
I02 = N : Disables all measuring and monitoring functions for
channel B.
I 03 Transducers
Choises : a, v
Function : Select transducer type.
I03 = a Use accelerometers.
I03 = v Use vibration velocity transducers.
Use the same pickup type with the same sensitivity for channel A
and B.
I 04 Unit
Choises : mV/g, mV/m/s
2
, mV/ips, mV/mm/s
Function : Define unit of pickup sensitivity.
I04 defines the unit of pickup sensitivity for both channels. If the
unit does not match the pickup type, VIBROCONTROL 1100 ge-
nerates error-message: -58.
Select
mV/g or mV/m/s
2
for accelerometers
mV/mm/s or mV/ips for vibration velocity transducers.