VC 1100 List of Setup Parameters
VC1100E/paralist Version 2 →
© Schenck VIBRO GmbH, D-64273 Darmstadt, Juni 98 C01 / C02 - C11 / C12 5-31
N 11 Relais K2 : Normally Energized
Choises : Y, N
Function : Select normally energized or normally de-energized
mode for relay K2.
Y = Relay K2 operates normally energized.
N = Relay K2 operates normally de-energized.
N 12 Relais K3 : Normally Energized
Choises : Y, N
Function : Select normally energized or normally de-energized
mode for relay K3.
Y = Relay K3 operates normally energized.
N = Relay K3 operates normally de-energized.
N 13 Relais K1 : Grenzwert-Verknüpfungen
Choises : OR, AND
Function : Define how several alarm level exceedances control
relay K1
OR = Exceedance of at least one of the
assigned alarm levels trips relay K1.
AND = Only exceedance of all assigned
alarm levels trips relay K1.
N 14 Relais K2 : Logic
Choises : OR, AND
Function : Define how several alarm level exceedances control
relay K2.
OR = Exceedance of at least one of the
assigned alarm levels trips relay K2.
AND = Only exceedance of all assigned
alarm levels trips relay K2.
N 15 Relais K3 : Logic
Choises : OR, AND
Function : Define how several alarm level exceedances control
relay K3.
OR = Exceedance of at least one of the
assigned alarm levels trips relay K3.
AND = Only exceedance of all assigned
alarm levels trips relay K3.