5
Startup
General
Operating Instructions – MOVIDRIVE
®
modular
154
5 Startup
5.1 General
DANGER
Uncovered power connections.
Severe or fatal injuries from electric shock.
Install the touch guards at the modules, see chapter "Covers"(→256).
Install the closing covers according to the regulations, see chapter "Cov-
ers"(→256).
Never start up the application inverter without installed closed touch guards and
closing covers.
5.1.1 Lifting applications
WARNING
Danger of fatal injury if the hoist falls.
Severe or fatal injuries.
The application inverter is not designed for use as a safety device in lifting applic-
ations. Use monitoring systems or mechanical protection devices to ensure
safety.
5.1.2 Connecting power
NOTICE
Undercutting the minimum switch-off time of the line contactor.
Irreparable damage to the application inverter or unforeseeable malfunctions.
The specified times and intervals must be observed.
After disconnection from the supply system, observe a minimum switch-off time
of 10 s.
Do not turn the power of the supply system on or off more than once per
minute.
5.1.3 Connecting cables
NOTICE
Cables may only be connected and disconnected in a de-energized state.
Irreparable damage to the application inverter or unforeseeable malfunctions.
Power plug connectors (motor, supply system braking resistor, brake) must only
be plugged in de-energized state.