Safety notes
Transport
Operating Instructions – MOVIDRIVE
®
modular
16
2.6 Transport
Inspect the shipment for damage as soon as you receive the delivery. Inform the ship-
ping company immediately about any damage. If the product is damaged, it must not
be assembled, installed or started up.
Observe the following notes when transporting the device:
• Ensure that the product is not subject to mechanical impact.
• Before transportation, cover the connections with the supplied protection caps.
• Only place the product on the cooling fins or on the side without connectors during
transportation.
• Always use lifting eyes if available.
If necessary, use suitable, sufficiently dimensioned handling equipment.
Observe the information on climatic conditions in chapter "Technical data" of the docu-
mentation.
2.7 Installation/assembly
Ensure that the product is installed and cooled according to the regulations in the doc-
umentation.
Protect the product from excessive mechanical strain. The product and its mounted
components must not protrude into the path of persons or vehicles. Ensure that com-
ponents are not deformed and that insulation spaces are maintained, particularly dur-
ing transportation. Electric components must not be mechanically damaged or des-
troyed.
Observe the notes in the chapter "Mechanical installation" of the documentation.
2.7.1 Restrictions of use
The following applications are prohibited unless explicitly permitted:
• Use in potentially explosive areas
• Use in areas exposed to harmful oils, acids, gases, vapors, dust, and radiation
• Operation in applications with impermissibly high mechanical vibration and shock
loads in excess of the regulations stipulated in EN61800-5-1
• Operation at installation altitudes above 3800 m above sea level
The product can be used at altitudes above 1000 m asl up to 3800m asl under the fol-
lowing conditions:
• Taking the reduced continuous rated current into consideration, see chapter
"Technical data" of the documentation.
• Above 2000 m asl, the air and creeping distances are only sufficient for over-
voltage class II according to EN60664. If the installation requires overvoltage cat-
egory III according to EN60664 you have to reduce the overvoltages on the sys-
tem side from category III to II using additional external overvoltage protection.
• If a protective electrical separation is required, then implement this outside the
product at altitudes of more than 2000m above sea level (protective separation in
accordance with EN61800‑5‑1 and EN60204‑1)
24748536/EN – 11/2017