Safety notes
Transport
Operating Instructions – MOVIDRIVE
®
modular
16
2.6 Transport
Inspect the shipment for damage as soon as you receive the delivery. Inform the ship-
ping company immediately about any damage. If the product is damaged, it must not
be assembled, installed or started up.
Observe the following notes when transporting the device:
Ensure that the product is not subject to mechanical impact.
Before transportation, cover the connections with the supplied protection caps.
Only place the product on the cooling fins or on the side without connectors during
transportation.
Always use lifting eyes if available.
If necessary, use suitable, sufficiently dimensioned handling equipment.
Observe the information on climatic conditions in chapter "Technical data" of the docu-
mentation.
2.7 Installation/assembly
Ensure that the product is installed and cooled according to the regulations in the doc-
umentation.
Protect the product from excessive mechanical strain. The product and its mounted
components must not protrude into the path of persons or vehicles. Ensure that com-
ponents are not deformed and that insulation spaces are maintained, particularly dur-
ing transportation. Electric components must not be mechanically damaged or des-
troyed.
Observe the notes in the chapter "Mechanical installation" of the documentation.
2.7.1 Restrictions of use
The following applications are prohibited unless explicitly permitted:
Use in potentially explosive areas
Use in areas exposed to harmful oils, acids, gases, vapors, dust, and radiation
Operation in applications with impermissibly high mechanical vibration and shock
loads in excess of the regulations stipulated in EN61800-5-1
Operation at installation altitudes above 3800 m above sea level
The product can be used at altitudes above 1000 m asl up to 3800m asl under the fol-
lowing conditions:
Taking the reduced continuous rated current into consideration, see chapter
"Technical data" of the documentation.
Above 2000 m asl, the air and creeping distances are only sufficient for over-
voltage class II according to EN60664. If the installation requires overvoltage cat-
egory III according to EN60664 you have to reduce the overvoltages on the sys-
tem side from category III to II using additional external overvoltage protection.
If a protective electrical separation is required, then implement this outside the
product at altitudes of more than 2000m above sea level (protective separation in
accordance with EN61800‑5‑1 and EN60204‑1)