EasyManua.ls Logo

SEW-Eurodrive MOVIDRIVE MDA90A-0640-503-X-S00

SEW-Eurodrive MOVIDRIVE MDA90A-0640-503-X-S00
288 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4
Installation
Electrical installation
Operating Instructions – MOVIDRIVE
®
modular
81
4.6.7 24V supply voltage
MOVIDRIVE
®
modular requires an external 24V supply voltage. Us the following in-
stallation material for the connection:
M4 fork-type or ring lugs with insulating collar and a cable cross section of max-
imum 4mm
2
,
or
M4 tubular cable lugs with insulating heat shrink tubing and a cable cross section
of maximum 6mm
2
.
24 V
GND
14476866443
Select the cross section of the supply cable according to the power demand of the
device to be supplied. Note the additionally required power of the directly supplied
24V brake for CMP motors with BK or BP brake without brake control.
The maximally permitted length of the 24V supply cable is 30m.
24748536/EN – 11/2017

Table of Contents