EasyManua.ls Logo

SEW-Eurodrive MOVIDRIVE MDA90A-0640-503-X-S00

SEW-Eurodrive MOVIDRIVE MDA90A-0640-503-X-S00
288 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9
Functional safety
Safety Conditions
Operating Instructions – MOVIDRIVE
®
modular
258
9.3.4 Requirements on startup
To validate the implemented drive safety functions, they must be documented and
checked after successful startup (validation).
Observe the restrictions for drive safety functions in chapter "Restrictions" for the
validation of the safety functions. Non-safety-related parts and components that af-
fect the result of the verification test (e.g. motor brake) must be deactivated, if ne-
cessary.
For using the application inverter in safety-relevant applications, it is essential that
you perform and record startup checks for the disconnecting device and correct
wiring.
9.3.5 Requirements on operation
Operation is only allowed within the limits specified in the data sheets. This prin-
ciple applies to the external safety controller as well as the application inverter and
approved options.
The built-in diagnostic function is limited in case of a permanently enabled or per-
manently disabled STO input. Only with a level change of the STO signal, exten-
ded diagnostic functions are performed. This is why the drive safety function via
STO input must be triggered with connected line voltage at least once every 12
months for PL d according to EN ISO 13849‑1 and SIL 2 EN 61800-5-2 and at
least once every 3 months for PL e according to EN ISO 13849‑1 and
SIL3EN61800‑5‑2 to achieve a complete test coverage. Adhere to the following
test procedure.
[1]
> 700 ms
> 700 ms
[3]
t
[2] [2] [2]
[4]
15205932683
[1] Maximum 12 months with PL d/SIL2
Maximum 3 months with PL e/SIL3
[2] Internal diagnostics
[3] High: No STO
[4] Low: STO active
To achieve complete test coverage after a device reset (e.g. after connecting the
line voltage), the test transition (STO active not active) can only be started >
700ms later. The device signals "ready for operation" or "STO – Safe Torque Off"
if it is not in fault state.
A detected hardware fault in the internal switch-off channels for STO will lead to a
locking fault state of the application inverter. If the fault is reset (e.g. by switching
the line voltage on/off or by a low level at the STO input for at least 30ms), a com-
plete test with internal diagnostics according to the above mentions test procedure
must be performed. If the fault occurs again, replace the device or contact the
SEW‑EURODRIVE Service.
24748536/EN – 11/2017

Table of Contents

Related product manuals