7
Service
Shutdown
Operating Instructions – MOVIDRIVE
®
modular
210
7.2.1 Procedure in case maintenance has been neglected
If you have not performed maintenance regularly, SEW‑EURODRIVE recommends
that you increase the line voltage slowly up to the maximum voltage. This can be
done, for example, by using a variable transformer for which the output voltage has
been set according to the following overview. After you have completed the regenera-
tion process, the device can be used immediately or stored again.
The following steps are recommended:
AC 400/500V devices:
• Step 1: 0V to AC 350V within a few seconds.
• Step 2: AC 350V for 15 minutes.
• Step 2: AC 420V for 15 minutes.
• Step 3: AC 500V for 1 hour.
7.3 Shutdown
To shut down the application inverter, de-energize the application inverter using ap-
propriate measures.
WARNING
Electric shock from capacitors that have not been fully discharged.
Severe or fatal injuries.
• Observe a minimum switch-off time of 10 minutes after disconnecting the power
supply.
7.4 Waste disposal
Observe the applicable national regulations.
Dispose of the following materials separately in accordance with the country-specific
regulations in force, such as:
• Electronics scrap (circuit boards)
• Plastics
• Sheet metal
• Copper
• Aluminum
24748536/EN – 11/2017