SLC Loop Ratings
The following ratings represent Shield Protocol SLCloops of the Aura Fire Alarm ControlPanel.
Connection Rating
LOOP (- OUT ), (+ OUT ) 27 V DC @ 400 mA
LOOP (- IN ), (+ IN ) 27 V DC @ 400 mA
Maximum Cable Capacitance:1 µF
Maximum Wiring Voltage Loss:6.4 V
Refer to SLC Loop Cabling for maximum allowable cable length calculations.
SHIELD Fire, Safety & Security Ltd
Aura Fire Alarm Control Panel Installation Manual
Version 1.00 |June 2019 |MAN-1431VS
Page 110
Appendix A: Specifications