For more information about the Aura Network Vision Annunciator, refer to the Aura Network Vision
Annunciator Information Guide (MAN-1434).
Media Gateway™ Panel Module (AUL-9088)
The Media Gateway™ is a communication panel module for the Aura Fire Alarm ControlPanel. It provides
connectivity to a remote monitoring center via Sur-Gard Fibro or dial-up. SIA is the recommended format for
usage, but Contact ID is also supported. Transmission can be made through one or two telephone lines, and/or
IP through Ethernet. Standard reporting codes have been pre-defined, although the user may customize these
codes through the Loop Explorer 2 programming application.
For more information about the Media Gateway Panel Module, refer to the Media Gateway Panel Module
Information Guide (MAN-1439).
8 Channel Relay Panel Module (AUL-9091)
The 8 Channel Relay Panel Modules have 8 voltage-free, unsupervised changeover relay contacts, each of
which can be individually programmed.
All outputs are configurable in the same way as devices connected to the loops and all may be acted upon by
cause and effect logic. These boards are typically used in applications which require more than the four standard
relay outputs, such as signaling to other systems or plant control.
For more information about the 8 Channel Relay Panel Module, refer to the 8 Channel Relay Panel Module
Information Guide (MAN-1440).
SHIELD Fire, Safety & Security Ltd
Aura Fire Alarm Control Panel Installation Manual
Version 1.00 |June 2019 |MAN-1431VS
Page 64
Overview