Loading Configuration
1. Load (or import) the appropriate configuration from Loop Explorer 2. After the import, the panel will begin
device initialization.
The node address must be set on the panel before importing a configuration from LE2.
2. Press Controls & Other Events >Other Events to display details of the ongoing device initialization
process.
3. Once initialization is complete, address any outstanding troubles that may be reported.
4. Confirm that the Fire System Normal condition is displayed.
Testing the Power Supply
Perform the following tests to confirm operation of the power supply:
1. Apply AC and battery power to the Aura Fire Alarm ControlPanel.
2. Check that the AC Normal LED is illuminated on the power supply.
3. Check that the Heartbeat LED is flashing on the power supply.
4. Remove AC power and ensure that the standby batteries are powering the fire control panel. The AC
Normal LED on the power supply switches off after 30 seconds to indicate the loss of power.
5. Reapply AC power to the Aura Fire Alarm ControlPanel.
6. Disconnect the red wire from the Standby Battery terminal. The Battery Disconnect LED on the Power
Supply illuminates and the fire control panel continues to operate.
7. Reconnect the red wire from the Standby Battery terminal.
Check connections and test voltages at the primary and secondary of the power supply if the panel does not
operate as described above.
Testing the Field Circuits
Perform the following field circuit tests to confirm proper connections of the loops, NACs, inputs, and outputs:
1. Connect external devices to field terminal loops, NACs, inputs, and outputs.
2. Confirm that correct connections exist between the batteries and the power supply.
3. Apply AC power to the Aura Fire Alarm ControlPanel.