COMPLIANCE INFORMATION
Underwriters Laboratories (UL)
Fire Alarm Equipment
SHIELD Fire, Safety & Security Ltd
The Aura Fire Alarm Control Panel is suitable as follows:
n Types of signaling services are automatic fire alarm and manual fire alarm
n Class A, B, and/or X Signaling Line Circuits
n Class Aand/or B for Notification Appliance Circuits
n Protected Premises Unit (PPU) for Local Service, Remote Station Service, Center Station Service,
Proprietary Service, Auxiliary Service.
NFPA
Install this product in accordance with NFPA 72, NFPA70, and NEC 70 and all local codes.
Install SLC detectors with spacing as specified in section NFPA 72. Units employing "multiple detector
operation" shall include guidelines for installing of a minimum of two detectors in each protected space and to
reduce the detector installation spacing to 0.7 times the linear spacing in accordance with National Fire Alarm
Code, NFPA 72.
All field wiring should be installed using fire rated cables according to the NFPA 72. Riser conductors shall be
installed in accordance with the survivability from attack by fire requirements in National Fire Alarm Code, NFPA
72, Section 12.3. Riser conductors shall employ either a 2 hour rated cable system, or meet requirements
approved by the AHJ.
FM Global Technologies LLC (FM APPROVALS)
SHIELD Fire, Safety & Security Ltd
SHIELD Fire, Safety & Security Ltd
Aura Fire Alarm Control Panel Installation Manual
Version 1.00 |June 2019 |MAN-1431VS
Page 12
Compliance Information