Model Number Series Description
STWC Exceder Multi-Candela Strobe Ceiling Mount White
STx Strobe - 15,15/75,30,75,95,110,135,185 cd, Wall
STxC Strobe - 15,30,60,75,95,115,150,177 cd, Ceiling
Riser conductors shall be installed in accordance with the survivability from attack by fire requirements in
National Fire Alarm Code, NFPA 72, Sections 6.8.6.3, and 6.9.4. Riser conductors shall employ either a 2 hour
rated cable system, or meet requirements approved by the AHJ, or installation of the Supervised Output Module
using NFPA Style 7 configuration.
SHIELD Fire, Safety & Security Ltd
Aura Fire Alarm Control Panel Installation Manual
Version 1.00 |June 2019 |MAN-1431VS