Chapter 7
MSC800
86 Operating instructions | SICK 8011540/14B8/2019-06-06
Subject to change without notice
Maintenance
7.5.3 Replacing the battery in the logic unit
The real time clock of the logic unit is powered by a battery (buffered if the supply voltage
of the MSC800 fails/is switched off). If this battery is flat, it has to be replaced (can be
identified when using the real-time clock in the process after restarting the MSC800: time
of the logic unit starts with 00:00).
1. Remove black plastic cover on the logic unit.
Fig. 37: MSC800: position of the battery in the logic unit
2. Remove the battery from the bracket and replace it with a new type CR2032 (3 V)
battery.
3. Put the black plastic cover back in place.
4. Dispose of the old battery as hazardous waste as per the ROHS directives (Europe).
5. Re-set the system time using the SOPAS-ET configuration software.
Setting the system time of the MSC800
The MSC800 must be connected to the SOPAS-ET configuration software.
1. Log in to the MSC800 in the “Service” user level using the password “Servicelevel”.
2. In the device tree, double-click on the SYSTEM entry.
3. In the REAL TIME CLOCK tab, click the SET REAL TIME CLOCK button.
4. Apply the settings in the dialog window.
5. Download to the MSC800.
Important
Requirements

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK MSC800 and is the answer not in the manual?

SICK MSC800 Specifications

General IconGeneral
BrandSICK
ModelMSC800
CategoryController
LanguageEnglish

Related product manuals